Number of connectable control heads and maximum length of the
bus line
I. ASI standard case
A maximum of 31 control heads can be attached to a bus line in the standard case.
According to ASI specifications the bus cable may be a maximum 100 m long.
NOTE
When using other cable diameters, the maximum cable length also changes (refer to ASI
specification).

Process data

Data bits for inputs (sensor and prox. switches):
Bit No.
Sensor
Bit 0
S1 (sensor 1)
Bit 1
S2 (sensor 2)
Bit 2
S3 (terminal for add. prox. switch)
Bit 3
Not used
Data bits for outputs (actuators and valves):
Bit No.
Valve
Bit 0
V1 (Valve 1)
Bit 1
V2 (Valve 2)
Bit 2
V3 (Valve 3)
Bit 3
Not used
Parameter bits: not used
22 - 1066
Value allocation
0 Prox. switch 1 OFF
1 Prox. switch 1 ON
0 Prox. switch 2 OFF
1 Prox. switch 2 ON
0 Prox. switch 3 OFF
1 Prox. switch 3 ON
always 0
Value allocation
0 Valve 1 OFF
1 Valve 1 ON
0 Valve 2 OFF
1 Valve 2 ON
0 Valve 3 OFF
1 Valve 3 ON
always 0