EntelliGuard G
stored in thermal memory resulting in a
reduction in the total circuit breaker tripping
time.
If the Circuit Breaker has tripped on a
overcurrent event the thermal effects of the
current previously running in the circuit will be
taken into account. (remembered). This can
result in a prevention of breaker re-closure onto
a circuit running in 'Hot conditions' or cause the
mentioned reduction in the total tripping time
after re-closure.
The trip unit tracks these occurrences across a
time frame of 12 minutes.
2.2.10 Neutral Protection
Four pole EntelliGuard G circuit breakers are
equipped with a neutral pole located on the left,
when viewed from the breaker front.
The EntelliGuard trip unit allows the neutral pole
to be optioned with or without a full set of
protection devices. When neutral protection is
chosen the LT (overload) protection device in the
neutral pole can be set at on of three different
values. Choosing neutral protection and the
value thereof depends on the network and
installation configuration.
The following options are available:
-- Neutral unprotected (0%)
-– Neutral protected and the LT protection set
at one of three values:
-- 50% Half Neutral protection
-- 63% Neutral Protection
-- 100% Full Neutral protection)
Setting the LT device in the Neutral pole
influences other installed protection devices (if
present) as indicated in table 2.16:
Table 2.16
Protection
Neutral setting
Device
LT
ST
100 %
I
RELT
Gf sum
LT
ST
63 %
I
RELT
Gf sum
LT
ST
I
50 %
RELT
Gf sum
LT
ST
I
0 %
RELT
Gf sum
2-24
INTRO
BREAKER
TRIP UNIT
augmentation de température. Lors du
fonctionnement normal, ces événements sont
enregistrés dans la mémoire thermique, ce qui
réduit le temps de déclenchement total du
disjoncteur.
Si le disjoncteur s'est déclenché sur un courant
de surcharge, les effets thermiques du courant
qui circulait précédemment dans le circuit seront
pris en compte. Cela peut éviter que le
disjoncteur ne se referme sur un circuit en «
conditions chaudes » ou réduire le temps total
de déclenchement après refermeture.
L'unité de protection enregistre ces
événements pour une durée de 12 minutes.
2.2.10 Protection du neutre
Les disjoncteurs EntelliGuard quatre pôles sont
équipés d'un pôle neutre situé sur la gauche
lorsqu'on est face à la face avant.
L'unité de protection de l'EntelliGuard permet de
protéger ou non le neutre. Lorsque la protection
du neutre est sélectionnée, la protection LT
(Temps long = surcharge) du pôle de neutre peut
être réglée sur trois valeurs différentes en
fonction de la configuration du réseau et des
installations.
Les options suivantes sont disponibles :
--Neutre non protégé (0%)
-- Neutre protégé et protection temps long
réglée sur l'une des trois valeurs suivantes :
-- Protection du neutre à 50%
-- Protection du neutre à 63%
-- Protection du neutre à 100%
Le réglage du temps long dans le pôle neutre
influence les autres dispositifs de protection (si
installés) comme indiqué dans le tableau 2.16:
Tableau 2.16
Device setting
in Neutral pole
Réglage du neutre
100%
100%
100%
100 %
100%
100%
63%
63%
63%
63 %
63%
63%
50%
50%
50%
50 %
50%
50%
0%
0%
0%
0 %
0%
0%
LOCKS
ACCESSORIES
Réglage de la
Protection
protection dans
le pôle neutre
LT
100%
ST
100%
I
100%
RELT
100%
Gf sum
100%
LT
63%
ST
63%
I
63%
RELT
63%
Gf sum
63%
LT
50%
ST
50%
I
50%
RELT
50%
Gf sum
50%
LT
0%
ST
0%
I
0%
RELT
0%
Gf sum
0%
TESTS
APPENDIX
veroorzaken. Bij normale werking worden deze
gebeurtenissen geregistreerd en opgeslagen in
een thermisch geheugen waardoor de totale
reactietijd van de schakelaar verlaagd wordt.
Indien de Vermogenschakelaar gereageerd
heeft op een overspanning, worden de
thermische effecten van de stroom die voordien
in het circuit stroomde in acht genomen.
(onthouden). Hierdoor kan een hersluiting van de
schakelaar vermeden worden bij een circuit dat
actief is in 'Warme omstandigheden' of de
vermelde verlaging van de totale reactietijd na
hersluiting veroorzaken.
De beveiligingsunit registreert deze gevallen
binnen een tijdsduur van 12 minuten.
2.2.10 Neutral Protection
(Nulstroombeveiliging)
Vierpolige EntelliGuard G vermogenschakelaars
zijn standaard uitgerust met een nulstroompool
aan de linkerzijde.
De EntelliGuard beveiligingsunit biedt de
mogelijkheid deze nulstroompool uit te rusten
met of zonder een volledige reeks
beveiligingsfuncties. Wanneer deze
nulstroombeveiliging gekozen is, kan de LT
(overspanning) beveiliging in de nulstroompool
ingesteld worden op drie verschillende waarden.
Het inschakelen van deze functie en de waarde
ervan is afhankelijk van de configuratie van het
netwerk en de installatie.
De volgende opties zijn beschikbaar:
-- Nulstroom onbeveiligd (0%)
-- Nulstroom beveiligd en de LT beveiliging
ingesteld op één van volgende drie waarden.
-- 50% Halve Nulstroombeveiliging
-- 63% Nulstroombeveiliging
-- 100% Volledige Nulstroombeveiliging
Instelling van de LT functie in de Nulstroompool
heeft een invloed op andere geïnstalleerde
beveiligingsfuncties (indien aanwezig), zie tabel
2.16:
Tabel 2.16
Functieinstelling
Beveiligingsfunctie
in
Nulstroominstelling
Nulstroompool
LT
ST
100 %
I
RELT
Gf sum
LT
ST
63 %
I
RELT
Gf sum
LT
ST
I
50 %
RELT
Gf sum
LT
ST
I
0 %
RELT
Gf sum
100%
100%
100%
100%
100%
63%
63%
63%
63%
63%
50%
50%
50%
50%
50%
0%
0%
0%
0%
0%