Digital
Output
32 33
O18 - AMF Relay
Settings RB
230V
>U : +10%
<U : -10%
Tt1 : 15s
Tt2 : 15s
6
4
+
-
12V
1
PE
N
L1
O17 - Aux.
O19 - Special signals
power socket
PE
N
L1
N
L1
PE
GB
GB
PE
N
L1
13
14
9
10
11
12
PE
N
L
GB
GB
220-277V
50-60Hz
O20 - Timer 7D
SETTINGS FOR N22:
N
L1 L2 L3
- Response value I1 = 30mA
O4 - ELR
Id>
O22 - ZBP
Connector
N
R
S
T
R1
R2
-X8
1
2
REMOTE
START
POSITION OF CONTACTS
K7
02.B8
R180
V-W : 400V
L1-L2 : 230V
A1
A2
SETTINGS FOR N23:
SETTINGS FOR N24:
- Response value I1 = 30mA (=50% I2)
- Response value 1/2 (alarm1/2) 10kOhm
- Relay operation mode: NO
- Fault memory M: ON
- Hysteresis 15%
- Operating mode K1/K2: NO
- Fault memory M: ON
- Starting delay: 1s
- Starting delay: 1s
- Response delay ton1: 0s
- Response delay ton1: 0s
- Pasword: off
- Delay on release: 1s
- Pasword: deactivated
O5 - RCMA420
O6 - ITR
-T22
-T23
Id>
R<
-K7
- 144 -
AC current CT
70
70
c2
F1
5+
71
c6
71
F2
6-
72
72
a0
V/L1
T2/T1
T2/T3:3PH
73
a0
73
T1/T10:1PH
-G3
42 43 44 46
W/L2
T3/T10
75
75
a0
X1
9/15
G
76
a0
76
X2
10/14
77
77
a0
Z1
11
78
a0
78
Z2
12/16
PE
N
U
V
W
-T1
P1
50
a8
S1
53
a8
S2
51
a8
S1
53
a8
S2
52
a8
S1
53
a8
S2
P2
R2
11
C2
12
14
U >
I>> I>> I>>
14
C1
11
-D1
17
18
a3
a3
02.E4
02.E4
02.E4
02.E4
03.C2
PE N
L1 L2 L3
Notes
Note 3: With "N- EDF", do NOT connect (N) to (PE) at X10.
T23 is to be mounted on the (PE) conductor,
between PE terminal and PE cooper bar.
O21 - N-EDF (see Note 3)
AC Voltage
GEN
34
35 36
37
(*)
TT
PE
PE-EDF
N
L1 L2 L3
(*) REMOVABLE PLATE