Wilo CronoLine-IL-E Notice De Montage Et De Mise En Service page 140

Publicité

Les langues disponibles

Les langues disponibles

en
No.
Name
5.7.2.0
Delivery head
correction for
monobloc pumps
5.7.5.0
Switching fre-
quency
5.7.6.0
SBM function
5.7.7.0
Factory setting
5.8.0.0
Other settings 2
5.8.1.0
Pump kick
5.8.1.1
Pump kick act-
ive/inactive
5.8.1.2
Pump kick time
interval
5.8.1.3
Pump kick speed
6.0.0.0
Error acknow-
ledgement
7.0.0.0
Access disable
Table 20: Menu structure
140
Installation and operating instructions • Wilo-CronoLine-IL-E, Wilo-CronoTwin-DL-E, Wilo-CronoBloc-BL-E • Ed.01/2024-02
Type Symbol
Values/explanations
If delivery head correction is active, the de-
±
viation of the factory-set differential pres-
sure measured by the differential pressure
sensor connected to the pump flange and
the different flange diameters are taken
into account and corrected.
Delivery head correction off
Delivery head correction on (factory set-
ting)
HIGH
High switching frequency (factory setting)
MID
Medium switching frequency
LOW
Low switching frequency
Setting for behaviour of signals
±
SBM run signal
SBM readiness signal
SBM mains on signal
OFF (default setting) Settings are not
±
changed when confirmed.
ON Settings are reset to factory setting
when confirmed.
Caution! All manual settings will be lost
ON (factory setting)
Pump kick is switched on
OFF
Pump kick is switched off
Can be set between 2 h and 72 h in 1 h
±
steps
Can be set between the pump's minimum
±
and maximum speeds
For additional information, see section "Ac-
±
knowledging errors".
Access disable inactive (changes possible)
±
(for additional information, see section "Ac-
tivating/Deactivating access disable").
Access disable active (no changes possible)
(for additional information, see section "Ac-
tivating/Deactivating access disable")
Display conditions
Only displayed in Δp-c and Δp-v
mode. Is not displayed for all pump
variants
Carry out the switchover/change
only when the pump is at a standstill
(not when the motor is running)
Is not displayed when access disable
active. Is not displayed when BMS is
active
Is not displayed when access disable
active. Is not displayed when BMS is
active For parameters that are
changed by a factory setting, see
section "Factory settings".
Not displayed if pump kick was de-
activated
Not displayed if pump kick was de-
activated
Only displayed if there is an error.