7.4.1
Permitted installation positions
with horizontal motor shaft
Fig. 14: Permitted installation positions with
horizontal motor shaft
Fig. 15: CronoBloc-BL-E
Installation and operating instructions • Wilo-CronoLine-IL-E, Wilo-CronoTwin-DL-E, Wilo-CronoBloc-BL-E • Ed.01/2024-02
The permissible installation positions for a horizontal motor shaft and electronic module
pointing upward (0°) are shown in Fig. 14.
Any installation position is allowed except for "electronic module facing down" (-180°).
Pumps vent optimally when the air vent valve points upward (Fig. 14, Item 1).
Discharge any condensate directly via the existing drilled holes, pump lantern and motor
(Fig. 14, Item 2).
For this purpose, remove the plug on the motor flange.
1
CronoLine-IL-E/CronoTwin-DL-E
2
CronoBloc-BL-E
Installation examples for CronoBloc-BL-E:
NOTICE
The installation position with a horizontal motor shaft is only permissible
for the CronoLine-IL-E/CronoTwin-DL-E up to a motor power of 15 kW.
No motor support is required.
For a motor power of >15 kW, only install with a vertical motor shaft.
NOTICE
Install monobloc pumps of the CronoBloc-BL-E series on a sufficient base
or mounting brackets (Fig. 15).
Motors with a motor power of 18.5 kW and higher require a support. See
installation examples.
For installations with a vertical motor position, the pump housing feet and
motor housing feet must be screwed on. This must be done stress-free.
Unevenness between motor and pump housing feet must be levelled out
for stress-free installation.
min. 5 mm
No support required
Pump housing supported
en
107