MAINTENANCE
Troubleshooting
Condition
Display
Runs But Trips
Low Pressure
Motor Frequency
High Pressure
Motor Frequency
Audible Noise
Motor Frequency
No Display
Cannot Connect to
Bluetooth Icon Off
Drive Bluetooth
RFI-EMI
Motor Frequency
Interference
42
Possible Cause
• Check fault code and
see corrective action
• Pressure sensor setting,
pump rotation, pump
sizing
• High temperature
• Pressure sensor setting
• Shorted sensor wire
• Fan, hydraulic, plumbing
• dV/dt filter
• Control Board cable
None
disconnected or loose
• Attempting to connect
to incorrect drive
• Out of Bluetooth range
of drive
• Poor grounding
• Wire routing
Corrective Action
• Proceed to fault code description and remedy
• Adjust pressure sensor, check pump rotation
• Check frequency at max flow, check max pressure
• High ambient and/or drive temperature will cause drive to
foldback power and run with reduced performance
• Adjust pressure sensor
• Remove sensor wire at Control Board, if drive stops running,
wire may be shorted
• Remove sensor wire at Control Board, if drive continues to
run, replace Control Board
• Remove sensor wire at new Control Board, if drive continues
to run, replace drive
• Verify condition of sensor wire and repair or replace if
necessary
• For excessive fan noise, replace fan
• If fan noise is normal, drive will need to be relocated to a
more remote area
• If hydraulic, try raising or lowering depth of pump
• Pressure tank location should be at entrance of water line into
house
• For EMI noise, change switching frequency to 8 kHz if using a
CEN model for surface applications, otherwise it is locked at
2.5 kHz.
• Verify cable connection between Power Board and Control
Board
• Ensure the Bluetooth SSID (Drive ID) you are connecting to
matches the drive you wish to connect to
• Bluetooth range is 100 feet line-of-sight, must be closer to
drive if walls or floors are between you and the drive
• Bluetooth module not responding, cycle power to drive
• Cycle Bluetooth radio on mobile device, refresh Bluetooth
connection list
• Adhere to grounding and wire routing recommendations
• An additional external filter may be needed.