ELECTRICAL INSTALLATION
Wiring Guidelines
Output (Motor) Wire Sizing
Submersible Pump Motors
Rated
Input
Model
Output
Phase
Volts
SDCP-SUB0723
SDCP-SUB1023
230
SDCP-SUB1523
SDCP-SUB0723
SDCP-SUB1023
230
SDCP-SUB1523
SDCP-SUB1043
SDCP-SUB1543
SDCP-SUB2043
460
SDCP-SUB2543
SDCP-SUB3043
A gray background indicates wire sizes that are larger than the maximum wire rating of the drive's terminal blocks.
External junction box required to splice cable sizes.
NOTE: 460VAC models with output motor cable lengths exceeding 1,000 feet require an additional load reactor or sine
filter to be installed between the drive output and the motor. The load reactor or sine filter should be rated for 3% voltage
drop in 460VAC applications and have a maximum amp rating suitable for the maximum output amp rating of the drive.
Centrifugal Pump Motors
Rated
Input
Model
Output
Phase
Volts
SDCP-CEN0723
SDCP-CEN1023
230
SDCP-CEN1523
SDCP-CEN0723
SDCP-CEN1023
230
SDCP-CEN1523
SDCP-CEN1043
SDCP-CEN1543
SDCP-CEN2043
460
SDCP-CEN2543
SDCP-CEN3043
A gray background indicates wire sizes that are larger than the maximum wire rating of the drive's terminal blocks.
External junction box required to splice cable sizes.
NOTE: 460VAC models with output motor cable lengths exceeding 1,000 feet require an additional load reactor or sine
filter to be installed between the drive output and the motor. The load reactor or sine filter should be rated for 3% voltage
drop in 460VAC applications and have a maximum amp rating suitable for the maximum output amp rating of the drive.
NOTE: Recommended for use on inverter duty rated motors. Follow motor manufacturer recommendations for cable
lengths when using variable frequency drives.
18
Rated
AWG 600V Copper Wire Sizes, 75° C Insulation, and Motor Cable Lengths (in feet)
Rated
Output
Output
14
Amps
HP
240
11
3
1
18
5
27
7.5
28
7.5
3
37
10
48
15
18
10
26
15
3
31
20
39
25
46
30
Rated
Rated
AWG 600V Copper Wire Sizes, 75° C Insulation, and Motor Cable Lengths (in feet)
Output
Output
14
Amps
HP
11
3
240
1
18
5
27
7.5
28
7.5
3
37
10
48
15
18
10
26
15
3
31
20
39
25
46
30
12
10
8
6
4
390
620
990
1540 2400 2980 3660
230
370
590
920
1430 1790 2190 2690 3290
420
650
1020 1270 1560 1920 2340 2870 3440
420
650
1020 1270 1560 1920 2340 2870 3440
310
490
760
330
520
500
790
1250 1960 3050 3800
850
1340 2090 2600 3200 3930
650
1030
1610 2000 2470 3040 3730
830
1300 1620 1990 2450 3010 3700
680
1070 1330 1640 2030 1490 3060 3700
12
10
8
6
4
390
620
990
1540 2400 2980 3660
230
370
590
920
1430 1790 2190 2690 3290
420
650
1020 1270 1560 1920 2340 2870 3440
420
650
1020 1270 1560 1920 2340 2870 3440
310
490
760
330
520
500
790
1250 1960 3050 3800
850
1340 2090 2600 3200 3930
650
1030
1610 2000 2470 3040 3730
830
1300 1620 1990 2450 3010 3700
680
1070 1330 1640 2030 1490 3060 3700
3
2
1
0
2/0 3/0
950
1170
1440 1760 2160 2610
650
800
980
1200 1470 1780
3
2
1
0
2/0 3/0
950
1170
1440 1760 2160 2610
650
800
980
1200 1470 1780