Menu Settings
To adjust system settings, make sure power is off and remove the
cover. Next, power the drive to make menu changes. When changes
are complete, power off the drive before replacing the cover.
Use the arrow keys to the right of the Display to navigate through
the setup menus.
•
The right arrow moves from screen to screen, and also functions
as an Enter key.
•
The up and down arrows scroll through the available options on
each screen.
•
When a selection has been made, you must press the Enter key
(right arrow) for the setting to take effect.
NOTE: If DIP SW1 – Position 1 is ON, settings can be made either manually through the VFD display, or
through the mobile app. Changes in either tool are reflected in the other. Power cycling the drive is not
required for menu based or DIP witch settings to take effect.
Menu Navigation
Home
Motor
Max Amps
Type
Submersible
Centrifugal
Home Screen: In normal operation, this screen displays the current system status. During setup, pressing
the Enter key (right arrow) changes the display to the Motor Type screen.
Motor Type: Configures the drive for the type of motor being used. Selecting SUB configures the drive for
use with a submersible motor. Selecting CEN configures the drive for an above-ground, centrifugal motor.
NOTE: SUB drive models can be configured for SUB or CEN pump/motor types. CEN drive models can
only be configured for CEN pump/motor type.
Max Amps: The Max Amps value is used to configure various protection features (pump underload, motor
overload, etc.). This value should match the Service Factor Amps or Maximum Amps rating listed on the
motor nameplate. During programming, the setting scrolls by 0.1A, then fast scrolls by 1.0A upon holding
down UP or DOWN button.
Sensor Type: Configures the drive for the type of pressure transducer or sensor being used. Selecting Trans-
ducer displays the Sensor Range screen. If a standard Pressure Sensor is selected, the target pressure is set using
the adjusting screw on the sensor itself. The System Response screen is displayed next for Pressure Sensor use.
Sensor Range: This is only configurable when the sensor type is transducer. This setting scales system oper-
ation to the installed transducer. The range is 100 to 300, with a default setting of 200 PSI. When changing,
the setting changes in 10 PSI increments.
Setpoints: There are user configurable setpoints in the system — Setpoint 1 and Setpoint 2. When the dual
setpoint input is open, setpoint 1 is the system/primary setpoint for the pressure control, and basis for the
overpressure trip setpoint. When the dual setpoint input is closed/shorted, setpoint 2 is the system/primary
setpoint for the pressure and basis for the overpressure trip setpoint.
Drive speed control is based on the difference between the system/primary setpoint and the transducer
feedback value. As user demand (flow) causes pressure changes, the drive varies the output frequency
Pressure Sensor Only
Sensor
Sensor
Setpoint 1
Type
Range
Transducer
Pres. Sensor
Transducer Only
Setpoint 2
Drawdown
System
Response
DRIVE CONFIGURATION
Menu Settings
Underload
Underload
Run/Stop
Sensitivity
Off Time
Input
QR Code
Press
Down
button to
view Fault
Logs 1-5