Electrical Connection; Supply Voltage - Biral AX RED Serie Instructions D'installation Et D'entretien

Pompe di circolazione biral
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

5. Electrical connection

Electrical connection should be carried out in accordance with the local regulations.
It is vital to ensure that the voltage and frequency indicated on the nameplate are compatible
with the mains supply available.
Warning
Before carrying out any electrical connection work,
the voltage supply must be switched off.
The pump must be connected to an external
network switch with a contact opening on all poles
of minimum 3 mm.
The protection against indirect contact can be
achieved by earthing or potential equalisation.
If the pump is connected to an electrical installa-
tion, which has an FI circuit breaker for additional
protection, the FI circuit breaker must trigger with
a pulsing direct current component if earthing fault
currents arise.
The FI circuit breaker must be marked with the
following symbol:
L
L
The pump does not require any external motor protection. The motor has integrated over-
tempe rature protection, which offers safeguarding against overloading that appears slowly
N
N
and against blocking according to IEC 34-11: TP 211.

5.1 Supply voltage

1×230V +6/-10%, 50 / 60 Hz, PE
The voltage tolerances are set for equalising voltage 0uctuations on the mains.
They are not for operating pumps with voltages other than those shown on the nameplate.
Legende:
Legende:
1 Sicherung (min.10A, träge)
1 Sicherung (min.10A, träge)
2 Externer Schalter
2 Externer Schalter
FI
FI
1
1
2
2
961807_01
961807_01
english
97
|

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ax blue serie

Table des Matières