Electric wire rope winch BETA 2.1 EL
English
4.8 Main current fuses / Feed cable / Circuit diagrams
The connection of the wire rope winch always has to be effected according to circuit and wiring dia-
grams included into delivery or to those provided on site
Each electric control will be delivered with corresponding circuit and wiring diagram!
Main current fuses must be provided on site.
Co-ordination recommended excess current devices and cross-sections with three-phase current
400V-50Hz (440V-60Hz)
driving power 50Hz P
[kW]
0,37
0,75
1,1
1,5
2,2
3,0
4,0
5,5
Attention!
When using longer cables one must consider an additional loss of current.
Consult your electrical engineer.
The connecting cables are to be laid in suitable cable channels or protection tubes.
Sharp edges, wire edges, rough surfaces or screw threads which the cable wires may come in to con-
tact with, must be removed from around the cable channels.
If a control is provided on site, the circuit diagram of the manufacturer has to be presented.
Observe the valid regulations.
The connection of the winch always has to be effected acc. to the circuit diagram included into de-
livery or to that provided on site!
Option CEE – Connector (assignment)
Pay attention to phase sequence and motor direction.
driving power
[kW]
< 2,0
< 5,0
< 11,0
4.9 Overload protection:
Winches with a load of 1000kg and more have to be equipped with an overload protection.
The contactor control for winches with a capacity of 1000kg and more will include the electronic overload
protection. The overload protection operates by means of a load-monitoring device, which is adjusted to
100% up to 110% of the driving power.
The mounted electronic overload protection works with a start bridging and do not release the operator to
check the carrying capacity and the charge.
Take care that the load does not interlock during the starting phase.
The overload protection does not operate by constant press-release in short intervals.
The electronic overload protection is a warning installation and it is not allowed for regular use to stop at
end positions. Use always path-dependent limit switches to stop at positions.
Take into consideration the rigidity of the complete lifting installation (inclusive frame etc.) in connection
with the max. overload time (start bridging, brake time, etc.) to determine the overload factor.
If the winch is integrated in a crane, the overload protection system for the complete system must be ana-
lysed by the manufacturer of the complete system and if necessary monitored by an additional load meas-
uring system.
The operator is not allowed to change the adjustment of the load monitoring device.
technische Änderungen vorbehalten
short circuit protection
nominal current
I
N
1,06
2,0
2,8
3,7
4,9
6,3
8,2
11,2
CEE – connector
[A]
16
32
63
design changes under reserve
04.01.601
rec. feed cable (sheathing halogen-
(fuse - inert)
[A]
4
6
6
6
10
16
16
25
rec. feed cable / min. cross-section
e. g. Oilflex – 540 P [mm²]
changements techniques sous réserve
free) cross-section
NYM-J [mm²] Cu
4x1,5
4x1,5
4x1,5
4x1,5
4x2,5
4x2,5
4x2,5
4x4
4 x 1,5
4 x 4
4 x 10