Troubleshooting the Anybus-S EtherNet/IP bus
module
LED indicators on
the Anybus-S
EtherNet/IP mod-
ule
LED connection /
Indicator
activity (1)
Lights up green
off
LED module sta-
Indicator
tus (2)
Lights up green
Flashing green
Flashing red
Steady red
Flashing green/red
off
LED network sta-
Indicator
tus (3)
Lights up green
Flashing green
Steady red
Flashing red
Flashing green/red
off
(1)
(2)
(4)
(3)
Meaning
Connection interrogated
Connection not interrogated
Meaning
Scanner monitoring in operation
Not configured or scanner idle
A minor, rectifiable, error has been detected
A fatal error has been detected
Self-test in progress
No power supply
Meaning
Online, one or more connections available (CIP category 1 or 3)
Online, no connections available
Duplicate IP address detected, internal error (Fatal error)
Timeout on one or more connections (CIP category 1 or 3)
Self-test in progress
No power supply or no IP address
(1)
Connection/activity
(2)
Module status
(3)
Network status
(4)
Activity