Relay output connection

1a
Function
X1/K11
NC contact
X1/K12
Centre contact
X1/K14
NO contact
PES
HF−shield termination by large surface connection to PE
)
Note!
Switching of control signals:
ƒ
Use shielded cables
HF−shield termination by PE connection
The minimum load for switching the signals through correctly is 12 V
and 5 mA. Both values have to be exceeded at the same time.
Switching of mains potentials:
ƒ
Unshielded cables are sufficient
For the protection of the relay contacts a corresponding suppressor circuit
ƒ
is absolutely required for an inductive or a capacitive load!
The service life of the relay depends on the type of load (ohmic, inductive
ƒ
or capacitive) and the value of the switching capacity.
The message that is output can be changed in code C0008 or C0415/1.
ƒ
EDK82MV371 DE/EN/FR 7.0
Fig. 5−1
Relay position
Open
Closed
l
Electrical installation
Relay output connection
X1
Message
Technical data
(Lenze setting)
TRIP
AC 250 V/3 A
DC 24 V/2 A ... DC 240 V/0.22 A
TRIP
5
8200 motec
X1
K11 K12 K14
PES
PES
8200mot058
103