Installation instructions, for professionals only
To install the safety cout-out device, perform the following steps:
1. Install the safety cut-out device in accordance with the operating instruc-
tions for the device.
2. Feed the wires for the safety cut-out device through the cable gland 6 into
the low-voltage connection area 1.
3. Connect the wires for the temperature sensor to the terminals labelled "OSG"
in terminal strip 2.
If a safety cut-out is not installed, a jumper must be fitted at the terminals
labelled "OSG".
5.12. Remote start
The remote start device is connected using terminals "S", "B" and "C". "S" stands
for sauna mode and "C" for evaporator mode. "B" is a +24 V DC output. The pre-
ferred operating mode must be activated using a switch or actuator on the terminal.
"S" and "C" can optionally be allocated to user program 1 and 2 (see "Remote
start" on page 38).
5.13. Status output
Any electrical device can be connected to the status output terminal which is
suitable for 24 V DC voltage and draws a current no greater than 200 mA. Make
sure the polarity is correct when connecting a device. If LEDs are used, a suit-
able series resistor must be used.
5.14. Finishing the installation
1. Connect the earth conductor for the power supply cable and all devices
to the earth bar g.
2. Place the cover of the housing on the upper edge of the junction box.
3. Push the clip locks inwards lightly, and turn the cover of the housing down-
wards until it engages audibly.