Warning messages

Installation and operating instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
Faults, causes and remedies
Code
Fault
409
Incomplete software
update.
Additional information about causes and remedy:
The pump can work only once the software update has been completed.
410
Voltage analogue input
overloaded.
Additional information about causes and remedy:
The fault impairs the binary inputs. EXT. OFF is set. The pump is stationary.
411
No mains phase
Additional information about causes and remedies:
Operation cannot be maintained. Possible causes:
1. Contact fault on mains connection terminal.
2. Fuse of a mains phase has tripped.
420
Motor or electronic
module defective.
Additional information about causes and remedy:
The pump cannot determine which of the two components is faulty. Contact
service.
421
Control module faulty.
Additional information about causes and remedy:
Contact service.
Table 55: Error messages
Warning displayed:
ƒ
The status display is marked in yellow.
ƒ
Warning message, warning code (W...), cause and remedy are described as text.
Display of a warning in 7-segment LED display:
Warnings indicate restricted pump function. The pump continues to operate in re-
stricted mode (emergency operation).
Depending on the cause of the warning, emergency operation leads to a restriction
of the control function and even reactivation of a fixed speed.
If the pump identifies as part of permanent monitoring that the cause of the warn-
ing no longer applies, the warning is revoked and operation resumes.
If a warning message is output, the display is permanently on and the green LED indic-
ator is off.
Code
Warning
550
There is flow through
the pump in the oppos-
ite direction of flow.
Additional information
about causes and rem-
edy:
If flow passing through
pump in the opposite
direction is too strong,
the motor can no longer
start.
551
Undervoltage
Cause
Remedy
The software update
Software update with a
was not completed.
new software bundle is re-
quired.
Voltage analogue in-
Check line and consumers
put short-circuited or
connected to power supply
too heavily loaded.
of analogue input for
short-circuit.
No mains phase
Checking the mains con-
nection
Motor or control
Replace motor and/or con-
module faulty.
trol module.
Control module
Replace the control mod-
faulty.
ule.
Cause
Remedy
External influences
Check power control of the
cause flow against
pumps,
the direction of the
install swing check valve if
pump's flow.
needed.
Power supply has
Check power supply.
dropped below 342 V.