en
202
Setting the control functions
Settings menu
Setting assistant
Heating/cooling switchover
Only visible if "Heating & Cooling" has
been selected in the setting assistant.
Heating/cooling temperature sensor
Only visible if automatic switchover is se-
lected in setting assistant "Heating &
Cooling" and "Heating/cooling
switchover".
Delivery head setpoint
Visible for active control modes, which re-
quire a delivery head as setpoint.
Setpoint volume flow (Q-const)
Visible for active control modes, which re-
quire a volume flow as setpoint.
Feeder pump correction factor
Visible for Multi-Flow Adaptation, which
offers a correction value.
Selection of secondary pumps
Visible for Multi-Flow Adaptation.
Multi-Flow Adaptation Overview
Visible for Multi-Flow Adaptation.
Volume flow offset
Visible for Multi-Flow Adaptation.
Multi-Flow Adaptation mixer
Visible for Multi-Flow Adaptation.
Substitute value volume flow
Visible for Multi-Flow Adaptation.
Setpoint temperature (T-const)
Visible for active control modes, which re-
quire an absolute temperature as set-
point.
Description
Setting the control mode via application
and system type.
Adjust the automatic or manual
switchover between heating and cooling.
When selecting "Heating/cooling
switchover" in the setting assistant you
must enter when the pump operates in
the corresponding mode.
In addition to a manual selection of
"Heating or cooling", options "Automatic"
or "Switchover through a binary input" are
also available.
Automatic: fluid temperatures are reques-
ted as decision-making criteria for the
switchover after heating or cooling.
Binary input: an external binary signal for
controlling of "Heating and cooling" is
queried.
Setting the temperature sensor for auto-
matic switchover between heating and
cooling.
Setting the setpoint of the delivery head
H
for the control mode.
S
Setting the volume flow setpoint for the
control mode "Volume flow Q-const"
Correction factor for the volume flow of
the feeder pump in the control mode
"Multi-Flow Adaptation".
The setting range differs depending on
the system type in the applications.
Can be used for a supplement to the total
volume flow from the secondary pumps
for additional protection against inad-
equate supply.
Selecting of secondary pumps which are
used for measuring the volume flow in
Multi-Flow Adaptation.
Overview of the number of connected
secondary pumps and their requirements.
Pumps without Wilo Net communication
can be supplied with an adjustable offset
volume flow in the Multi-Flow Adaptation
system.
In the case of secondary pumps in circuits
with mixers, the mixed volume flow can
be determined and therefore the actual
demand can be ascertained.
Setting of the substitute value for the
volume flow requirement for the primary
pump if the connection to the secondary
pumps is interrupted.
Setting the setpoint of the temperature
for the control mode "Constant temper-
ature (T-const)".
WILO SE 2021-12