3. install pneumatic connection between control head and actuator
Figure 13:
Installing the pneumatic connection
Screw the plug-in hose connectors onto the control head and the actuator.
Using the hoses supplied in the accessory kit, make the pneumatic connection between the control head and
actuator with the following "Table 1: Pneumatic connection to actuator".
noTe!
damage or malfunction due to ingress of dirt and moisture!
• To comply with protection class IP65 / IP67, connect the pilot air outlet (only for CFA or CFB) which is not
required to the free pilot air port of the actuator or seal with a plug.
"In rest position" means that the pilot valves of the control head Type 8695 are isolated or not actuated.
If the ambient air is humid, a hose can be connected between pilot air outlet 2
the unconnected pilot air port of the actuator for control function A or control function B. As a result, the
spring chamber of the actuator is supplied with dry air from the vent duct of the control head.
22
Pilot air outlet 2
Pilot air outlet 2
Upper pilot air port
Lower pilot air port
english
Type 8695
Installation
1
2
2
of the control head and