Type 8695
Installation
noTe!
damaged printed circuit board or malfunction!
• Ensure that the puck holder is situated flat on the guide rail.
Push the control head onto the actuator. The puck holder must be aligned in such a way that it is inserted into
the guide rail of the control head.
Press the control head all the way down as far as the actuator and turn it into the required position.
Ensure that the pneumatic connections of the control head and those of the valve actuator are situated
preferably vertically one above the other (see "Figure 12: Installing the control head").
If they are positioned differently, longer hoses may be required other than those supplied in the accessory
kit.
Figure 12:
Installing the control head
noTe!
too high torque when screwing in the fastening screw does not ensure protection class ip65 / ip67!
• The fastening screws may be tightened to a maximum torque of 0.5 Nm only.
Attach the control head to the actuator using the two side fastening screws. In doing so, tighten the fastening
screws hand-tight only (maximum torque: 0.5 Nm).
Fastening screws
max. 0.5 Nm