LAYOUT DIAGRAM AND CONNECTIONS

Fig.1
J4
F1
M5
L
N
PH
N
TRANSFORMER
J1 terminal lock (12 pin):
1-2 Electric lock - 12 V AC output with maximum connectable load of 15W controlling the electric lock for approx. 1.5 seconds
in the opening stage.
3-4 Flashing LED, 24 V DC- two-wire cables with min. section 1 mm
5-4 Warning light - 24 V DC output with maximum load of 3W for gate warning light.
6-9 Opening safety (NC safety contact) or pedestrian start (NO).
7-9 24 V power supply for accessories
8-9 Closing photocells input (NC safety contact)
10-9 STOP (NC safety contact) to stop wing.
12-11 START (NO) starts wing opening and closing.
J3 power terminal block with inputs for two 24 V DC motors - two-wire cable with min. section 1.5 mm
J4 connector for 230 V AC connection
M5 230 V AC phase-earth-neutral connection
FS1 24 V AC connection
CN1 3-pin Aprimatic connector for accessories ( UNICO receiver, access control decoder, etc.)
CN2 10-pin connector for PL-ECO receiver
BATT 24 V DC battery connection
F1 fuse for primary transformer protection
F2 fuse for external accessory protection (24 V DC)
F3 fuse for electronic circuit protection
DISPLAY (7 segments and one dot) to display parameters and parameter values
S1 RED button = Confi rm (used before self-teach to actuate motor 1 in the Person Present mode)
S2 YELLOW button = Exit (used also to display connections on display)
S3 BLUE button = Scroll the values available (used before self-teach to actuate motor 2 in the Person Present mode).
DL1 LED indicating that the board is powered up
RSK24-2000/2500
F2
F3
FS1 BATT
-
+
24 V AC
BATT
LEGEND:
M1 = motor 1st wing or single wing opening
M2 = motor 2nd wing opening
= NO type contact
= NC type contact
DL1
J3
M1 M2 M3 M4
1
2
-
M1
M2
MOTOR
MOTOR
1
2
12 Vac 15 W max.
CAUTION! When the NC contacts are not used, they must
be jumpered to the earth terminal (terminal 9 or 11). If you
do not do this the automation WILL NOT work.
NOTE: The default setting for terminal 6 is NO (normally
open). It can be set to NC (normally closed) by setting
parameter H (sect. 7.1).
2
. DO NOT use other types of fl ashing light.
- 17 -