STARTING UP AND PROGRAMMING
Step 4 (menu 4): sensitivity in opening
Adjust this parameter to the lowest possible
value compatible with the correct operation of
the facility. The operator therefore has greater
sensitivity to detect a possible collision of the
door with an obstacle (see "Obstacle detection
functioning" on page 39).
Step 5 (menu 5): sensitivity in closing
Adjust this parameter to the lowest possible
value compatible with the correct operation of
the facility. The operator therefore has greater
sensitivity to detect a possible collision of the
door with an obstacle (see "Obstacle detection
functioning" on page 39).
56
Installation guide
1 With the display showing 4, press SET once:
number 4 will start flashing on the display (this is the
preset value for this parameter).
2 Pressing the |+ and |- buttons, select the value
required for the opening sensitivity of the operator
(sensitivity for obstacle detection during opening):
1: maximum sensitivity
2, 3, 4, 5: intermediate values
6: minimum sensitivity
3 Once the required value is selected, press SET to
confirm and save it.
M278P4
4 Press the |+ button once to access the next
programming step.
In steps 4 to 12 (menu 4 to 12), programming can
be finished in advance by holding down SET (until
CL is displayed), without having to continue
advancing using the |+ button.
1 With the display showing 5, press SET once:
number 4 will start flashing on the display (this is the
preset value for this parameter).
2 Pressing the |+ and |- buttons, select the value
required for the closing sensitivity of the operator
(sensitivity for obstacle detection during closing):
1: maximum sensitivity
2, 3, 4, 5: intermediate values
6: minimum sensitivity
3 Once the required value is selected, press SET to
M278P5
confirm and save it.
4 Press the |+ button once to access the next
programming step.
In steps 4 to 12 (menu 4 to 12), programming can
be finished in advance by holding down SET (until
CL is displayed), without having to continue
advancing using the |+ button.