3 INSTALLATION
3.2.11 Wiring of a wall-mounted version, 115/230 VAC, with relays
Install the transmitter as described in § 3.1.3. Unscrew the 4 screws of the cover and uns-
crew the cable glands. Pass the cables through the cable glands by preferably respecting
the allocation indicated in fig. 3.14. Connect according to pin assignment below.
Only manipulate the switches when the device is not powered.
Sourcing / sinking mode switch
(*) wired ex-works
Without
With
Fit here the
cables using the
supplied cable
clips
1 2 3 4 PE
(see § 3.2.3)
PT SENSOR
Temperature sensor
connection:
1 : red wire
2 : blue wire
3 : white wire
4 : green/yellow wire
PE : shielding of the
cable
1
2
Pt1000
3
4
PE
Equipotential of the medium
Fig. 3.18 Wiring of the transmitter, wall-mounted version, 115/230 VAC, with relays
Connection of
the shielding of
the power supply
cable *
CURRENT
SOURCE
SINK
1 2 3 4
PE
NC
L+
L-
PE
Iout
L+
L-
PE
Supply
12..30Vdc
PH SENSOR
3A/230VAC
pH sensor connec-
tion
E-22-
PH TRANSMITTER 8205
All the cables must
be fitted here
Fuse
5 6 7 8 9 10
+ -
Strap to be
removed if the
4-20 mA
4-20 mA output
is used
PLC
230/115 VAC
power supply
selection switch
L N
Connect the
115/230 VAC
power supply