Operating The Engine
Deep Sea Controller
To start the engine
1. Turn the Deep Sea control module On / Off switch (A,
Figure 13) to the 'On' position.
2. To manually start the engine *:
Push the 'Start' button on the Deep Sea control
module (B, Figure 13) two times (2x).
After the intake heater has warmed the intake,
the engine will start.
3. After the engine has started, the circuit breakers need
to be in the 'On' position.
WARNING
Automatic Engine Start Hazard
Unexpected start of engine could result in death or
serious injury. Read and follow electronic controller
operator's manual before operating or servicing this
equipment.
13
Ref
Description
A
Deep Sea Mode Switch
B
Deep Sea Unit
To shut down the engine
1. Push the 'Stop' button on the Deep Sea control
module.
*Note: For complete information on the Deep Sea control
module, read the Deep Sea control module operator's
manual.
Automatic Engine Shutdown System
The engine is equipped with an automatic engine
shutdown system to prevent excessive engine damage in
the event of low oil pressure or high coolant temperature.
For additional information, refer to the engine operator's
manual.
14
Auxiliary AC Outlet
Auxiliary AC outlets (A, B, and C, Figure 14) are located
on the right rear of the machine. Each outlet is protected
by a spring- loaded cover.
Note: Outlets may differ according to model.
Power is supplied to the outlet(s) only when the engine is
running and the main circuit breaker (D, Figure 14) is in
the ON position.
Note: The electrical system is designed with a 20-second
delay after the engine starts before the auxiliary AC
outlet(s) will operate.
Each outlet is protected by a dedicated circuit breaker
(E, F, and G, Figure 14) found on the AC Outlet Circuit
Breaker Control Panel.
Note: Circuit breakers differ according to outlets provided.
If a Breaker Trips
Power is supplied to the outlets when the engine is
running and the main breaker is ON.
Each outlet is protected by a dedicated circuit breaker. If
a breaker trips:
1. Disconnect the load from the outlet.
2. Shut down the engine.
3. Wait 10 minutes for the generator to cool down.
A
4. Correct the load problem.
5. Start the engine.
6. Reset the breaker.
Note: Be sure to also check the GFCI breaker on the
GFCI outlet (if equipped), and reset if necessary.
7. Reconnect the load.
8. If the problem persists, see Troubleshooting.
B
14
D
G
See Figure 15 and the table following for the types of
available outlets.
E
F
A
B
C
www.allmand.com