Fonctions DP-V1
6
Structure du canal paramètres DP-V1
0 0
Codes retour
PROFIdrive pour
DP-V1
60
Le tableau suivant montre le codage du numéro d'erreur ( Error number ) dans la
réponse-paramètres DP-V1 selon le protocole PROFIdrive V3.1. Les données de ce ta-
bleau s'appliquent lorsque les fonctions PROFIdrive Request parameter ou Change pa-
rameter sont en cours d'utilisation.
Error No.
Meaning
0x00
Impermissible parameter
number
0x01
Parameter value cannot be
changed
0x02
Low or high limit exceeded
0x03
Faulty subindex
0x04
No array
0x05
Incorrect data type
0x06
Setting not permitted (can
only be reset)
0x07
Description element cannot
be changed
0x08
reserved
0x09
No description data
available
0x0A
reserved
0x0B
No operation priority
0x0C
reserved
0x0D
reserved
0x0E
reserved
0x0F
No text array available
0x10
reserved
0x11
Request cannot be execu-
ted because of operating
state
0x12
reserved
0x13
reserved
0x14
Value impermissible
0x15
Response too long
0x16
Parameter address
impermissible
0x17
Illegal format
Manuel Carte de pilotage MOVI-PLC® DHP11B pour MOVIDRIVE® MDX61B
Used at
Access to unavailable parameter
Change access to a parameter value
that cannot be changed
Change access with value outside the
value limits
Access to unavailable subindex
Access with subindex to non-indexed
parameter
Change access with value that does not
match the data type of the parameter
Change access with value unequal to 0
where this is not permitted
Change access to a description element
that cannot be changed
(PROFIdrive Profile V2 : PPO-Write
requested in IR not available)
Access to unavailable description
(parameter value is available)
(PROFIdrive Profile V2 : Access group
wrong)
Change access without rights to change
parameters
(PROFIdrive Profile V2 : wrong
password)
(PROFIdrive Profile V2 : Text cannot be
read in cyclic data transfer)
(PROFIdrive Profile V2 : Name cannot
be read in cyclic data transfer)
Access to text array that is not available
(parameter value is available)
(PROFIdrive Profile V2 : No PPO-Write )
-
Access is temporarily not possible for
reasons that are not specified in detail
(PROFIdrive Profile V2 : other error)
(PROFIdrive Profile V2 : Data cannot be
read in cyclic interchange)
Change access with a value that is within
the value limits but is not permissible for
other long-term reasons (parameter with
defined single values)
The length of the current response
exceeds the maximum transmittable
length
Illegal value or value which is not sup-
ported for the attribute, number of ele-
ments, parameter number or subindex or
a combination
Write request : Illegal format or format of
the parameter data which is not
supported
Supplem. Info
0
Subindex
Subindex
Subindex
0
0
Subindex
Subindex
-
0
-
0
-
-
-
0
0
Subindex
0
0
0