Signal output
There are two separate current outputs: conductivity and temperature. These are set in
the 'Setup' for the 'Current Allocation' .
Under 'Current Allocation' in the 'Setup' menu, you can select between 0–20 mA or
4–20m A (selected using the
Example 1:
Measured conductivity:
15 mS/cm à IA = 15 mA
Example 2:
Measured conductivity:
125 mS/cm à IA = 0.08 mA/mScm-1 x 125 mScm-1 + 4 mA = 14 mA
Ä Chapter 7.2 'Set-up' on page 44
key, active setting flashes).
37
Layout and installation
MAN049432 Rev. 03-03.2024