Fig. 1 --- Service area (top view) / Area di servizio (vista dall'alto)
1500
NOTES:
Minimum distances between 2 units from condensing coil side = 3 m
Do not obstruct the air exiting from fans for a minimum distance of 2,5 m
NOTE:
Distanza minima tra 2 unità lato batteria condensante = 3 m
Non ostacolare l'aria in uscita ventilatori per una distanza di almeno 2,5 m
Fig. 2 --- Victaulic connection system / Sistema di connessione Victaulic
DIMENSIONS / DIMENSIONI
OD
A
Tolerance
Toleranza
B
Tolerance
Toleranza
C
D
Tolerance
Toleranza
For welded hydraulic connection use the "line sections"
supplied, otherwise directly connect grooved lines with
the Victaulic---type joints of the unit, taking care to suita-
bly grease the joint gaskets
2 Compressor Unit
Unità a 2 Compressori
AIR
ARIA
AIR
ARIA
Ø
4"
5"
DN
100
125
Ømm
114,3
139,7
mm
15,88
15,88
mm
±0,77
±0,77
mm
9,53
9,53
mm
±0,77
±0,77
mm
2,11
2,13
Ømm
110,08
135,50
mm
---0,51
---0,56
mm
+0,00
+0,00
Ordinary Maintenance Area
Area di Manutenzione Ordinaria
Extraordinary Maintenance Area
Area di Manutenzione Straordinaria
1500
Unit pipe
Tubazione unità
6"
150
168,3
15,88
±0,77
9,53
±0,77
2,16
163,96
---0,56
+0,00
Per il collegamento idraulico con saldatura utilizzare i
"tronchetti" di tubazione" forniti a corredo, altrimenti
collegarsi direttamente con le tubazioni scanalate ai giun-
ti tipo Victaulic dell'unità avendo cura di ingrassare ade-
guatamente le guarnizioni del giunto.
10
Small pipe kit not fitted
Tronchetto di tubazione fornito a corredo
B
A
150