04.F8
04.F8
04.F8
04.F8
04.F8
PE
N
L1
L2
L3
PE
N
L1
L2
L3
(canopy)
(canopy)
O11 - Power Locks
O11 - Power Locks
Table 10 - Wire marking
Socket
L1
L2
L3
N
X2
N/A
N/A
N/A
N/A
X3
N/A
N/A
N/A
N/A
X4
4L1
4L2
4L3
4N
X5
5L1
5L2
5L3
5N
X6
6L1
6L2
6L3
6N
X7
7L1
7L2
7L3
7N
X8
8L1
8L2
8L3
8N
X9
9L1
9L2
9L3
9N
X10
10L1
10L2
10L3
10N
X11
11L1
11L2
11L3
11N
Table 11 - 1PH socket connection
Phase
Socket slot
Socket 1
Socket 2
Socket slot 1
X2
L1
X3
Socket slot 2
X4
L3
X5
Socket slot 3
X6
L2
X7
Socket slot 4
X8
L1
X9
Socket slot 5
X10
L3
X11
C
o
f n
Socket type
Socket slot 1
2x16 1PH or 2x16 3PH or 2x32 3PH
Socket slot 2
2x16 1PH or 2x16 3PH or 2x32 3PH
Socket slot 3
2x16 1PH or 2x16 3PH or 2x32 3PH
Socket slot 4
2x16 1PH or 2x16 3PH or 2x32 3PH
Socket slot 5
2x16 1PH or 2x16 3PH or 2x32 3PH
O12 - Sockets
O2 - Dual
frequency
C2
C2
U >
U >
C1
C1
123
123
L1 L2
L3
N
PE
NOTES
Table 12 - Cross-section/colour
Note 7: This representation of the sockets option is only one example of connection. Several configurations can be made.
Phase
L1-L2-L3
Note 8: See Table 10 for wire marking.
Socket
N
PE
Note 9: See Table 12 for wire cross-section and colour.
L2
16A 1PH
c0
c6
c54
Note 10: Connect 1PH sockets alternating the connection line as shown Table 11.
L1
16A 3PH
c0
c6
c54
Note 11: Two types of circuit breakers migth be selected: magnet-thermal circuit breaker or earth leakage (ELCB) circuit breaker. With 1PH sockets only ELCB can be
L3
32A 3PH
e0
e6
e54
Note 12: In each socket slot migth be fitted 2 sockets with exception of 63A and 125A sockets, in this case only one socket per slot is allowed. 63A and 125 sockets can only
L2
63A 3PH
fx0
fx6
fx54
gx0
gx6
L1
125A 3PH
h54
g i
r u
t a
o i
n
s
t e
1
C
o
f n
g i
r u
t a
o i
n
Socket
Circuit braker
Socket type
Label
label
X2, X3
Q2, Q3
2x16 1PH or 2x16 3PH or 2x32 3PH
X4, X5
Q4, Q5
2x16 1PH or 2x16 3PH or 2x32 3PH
X6, X7
Q6, Q7
2x16 1PH or 2x16 3PH or 2x32 3PH
X8, X9
Q8, Q9
2x16 1PH or 2x16 3PH or 2x32 3PH
X10, X11
Q10, Q11
1x63 3PH or 1x125 3PH
C2
U >
C1
16 A
30 mA
T
30 mA
123
L1 L2
L3
N
PE
mounted. With 63A and 125A sockets, an earth leakage add-on blockis used when ELCB type is selected.
be mounted in slots 3, 4 or 5. There are 4 configuration sets depending on number of the 63A/125A sockets selected: No 63A/125A sockets, 1 unit 63A/125A
socket, 2 units 63A/125A sockets, 1 unit 63A socket and 2 units 63A/125A sockets. Table 13 shows the 4 configurations sets with the corresponding markings of
sockets and circuit breakers.
Table 13 - Socket configuration set
s
t e
2
C
o
f n
g i
r u
t a
o i
n
s
t e
3
Socket
Circuit braker
Socket
Socket type
Label
label
Label
X2, X3
Q2, Q3
X2, X3
2x16 1PH or 2x16 3PH or 2x32 3PH
X4, X5
Q4, Q5
X4, X5
2x16 1PH or 2x16 3PH or 2x32 3PH
X6, X7
Q6, Q7
2x16 1PH or 2x16 3PH or 2x32 3PH
X6, X7
X8, X9
Q8, Q9
1x63 3PH or 1x125 3PH
X10
X11
Q11
1x63 3PH or 1x125 3PH
X11
- 122 -
C2
C2
U >
U >
I>>
I>>
I
I
C1
C1
16 A
16 A
30 mA
30 mA
123
L1
L1
N
N
PE
PE
C
o
f n
g i
r u
t a
o i
n
s
t e
4
Circuit braker
Socket
Circuit braker
Socket type
label
Label
label
Q2, Q3
X2, X3
Q2, Q3
2x16 1PH or 2x16 3PH or 2x32 3PH
Q4, Q5
X4, X5
Q4, Q5
2x16 1PH or 2x16 3PH or 2x32 3PH
Q6, Q7
1x63 3PH
X9
Q10
1x63 3PH or 1x125 3PH
X10
Q10
Q11
1x63 3PH or 1x125 3PH
X11
Q11
I>>
I
L1
N
PE
F
Q9