14.3 Local commands
Local commands are self-held in the standard configuration. The control only
needs to be pressed once to perform an open or close command.
To override this feature and require open or close commands to
be held down throughout the action:
Select change from the menu and turn to OK to confirm.
Select commands in the CHANGE menu and turn to OK to confirm.
Select local command in the COMMANDS menu and turn to OK to
confirm. Select (maintained) and turn to OK to confirm.
For a local command with increments from 0 to 100%, select (0 –
100%).
The command then takes the value of the current position and is
displayed under the position. The right-hand selector can then be
used to change the command value in increments of 1%.
14.4 Local stop
The actuator can be stopped locally in the standard configuration, even if it
is set on remote control.
 To disable the local stop action when the selector is on remote,
select local stop in the COMMANDS menu and then select (no).