9 REMOTE CONTROL
The INTELLI+ actuator remote control system can be operated using an
external or an integral voltage supply.
The input circuits are fully opto-isolated.
The self-hold pulse command system requires four connecting wires on the
client terminal strip: Common, stop, open and close. If the stop push-button
is not used, do not connect the STOP wire, open (or close) contact must be
maintained to operate the actuator.
Dry contact control
In case of dry contact control, a jumper must be fitted across customer
terminal 5-6.
Voltage control
Remote control can use either in AC or DC voltage.
Use common terminal 5 for low voltages from 10 to 55V. Use common
terminal 4 for voltages from 55 to 250V.
!
Never connect voltage sources above 55V on common terminal 5.
14