For the actuators equipped with battery option.
During the storage period, the circuit is in low consumption mode which
allows to get a long lifetime of the battery. Beyond a storage time of 3 years,
it is better to replace the batteries at the commissioning.
You can check the battery status at any time on the display.
4 MANUAL OVERRIDE AND DECLUTCHING
The handwheel does not turn during electrical operation.
SQ6 and SQ15 models:
These actuators are equipped with a manually
declutchable handwheel.
 To operate manually the actuator, turn
while
mechanically engage it.
To declutch the handwheel, just push it back
towards the actuator body.
SQ20 to SQ80 models:
To ease the manual override, some of these actuators are equipped with
declutchable intermediate gears. By moving the clutch lever, the motor is
physically disengaged from the gears. Once the manual handwheel operation
has been completed, do not forget to clutch the motor back. Otherwise,
once started-up, it would run and heat up until the motor thermal protection
switch closes. If repeated, these conditions can generate a motor
breakdown.
SQ100 to SQ1000, ST6 and ASM models:
These actuators are provided with an automatic
declutching handwheel, with motor drive priority.
To operate manually the actuator, turn the arrow
of the handwheel clutch button in front of the
triangular sign on the housing (it might be
necessary to turn the handwheel by a few degrees
to release the claws).
When the motor starts, it returns automatically into declutched position.