17 CUSTOMIZING
INDICATIONS
17.1 Local indication
The local display can be configured as
follows:
Invert display:
The display can be inverted (rotated
180°).
Select Change in the menu, then
signaling, then local then invert display (yes).
Display torque:
Select this option to have the real-time torque value displayed on the
actuator display at the same time as the position.
Select Change in the menu, then signaling, then local then display torque
(yes).
Red & Green LEDs:
In the standard configuration, the red light indicates that the valve is closed,
and the green light means it is open. The assigned colors can be changes so
that the red light indicates that the valve is open and the green one means
it is closed.
Select change in the menu, then signaling, then local then lights:
Red=(open).
To keep the valve open and valve closed labels in the correct
position on the indicator, you must also open the cover with the
window and turn round the display indicator plate.
17.2 Remote indications
Signals giving actuator status data are transmitted via bi-stable relays. Each
relay can be configured applying a list of available options.
INTELLI+ has 4 bi-stable relays in the standard configuration. A further 3 bi-
stable relays can be added as an option (the contact is open when there is
no power).
The equipment is configured at the factory in accordance with the order.
English
STATUS
LOC INDICATION
return
opposite display
torque display
lights
return
Torque 60%