23 USING ANALOG POSITION SIGNAL (OPTION)
On some models, the actuator can use an analogue signal to transmit its
percentage position (0 - 100%) to a remote device.
The output signals are automatically calibrated on the actuator's stroke (0-
100%) and so the transmitted position signal does not need any adjustment.
The transmitted signals are totally isolated from the INTELLI+ circuits.
Use
a
rectified,
stabilized 12-32V DC power supply
for this position signal. In case of 2-
wire connection, it is also possible
to use the internal 24V power
supply on terminals 6(-) and 7(+).
See the table for max. allowed
load.
The following signals can be used: 4-20 mA, 0-20 mA, 4-12 mA, 12-20 mA.
4-20 mA, 4-12 mA or 12-20 mA
outputs can be connected with
two wires, with the external
power supply in series with the
signal
reading.
circuit diagram) The 0-20 mA
output can be used to obtain a 0-
10V signal using an external 500
ohm (or 499 ohm 1%) resistor.
The power supply voltage will be 15 to 32V.
To select the signals' direction of variation and type
Select change in the MENU and turn to
OK to confirm.
Select position in the CHANGE menu
and turn to OK to confirm.
Select opt. posit. signal in the
POSITION menu and turn to OK to
confirm.
Choose signal's direction of variation
and turn to OK to confirm.
Select signal type and turn to OK to
confirm.
filtered
or
(see
actuator
English
Power supply
(V)
12
24
30
0-10 V position remote signal
OPT POSIT SIGNAL
Signal (
Signal (
SIGNAL (
(4-20 mA)
(0-20 mA / 0-10V)
(4-12 mA)
(12-20 mA)
51
Max allowed load
(ohms)
150
750
1050
) opening
) opening
) OPENING