18 CUSTOMIZING FAULT RELAY
Fault signals are sent via a changeover relay which is normally energized and
returns to the break position if power is lost or if the actuator is unavailable.
This relay can be configured applying a list of options, that are set at the
factory according the order.
Changes can be made as follows:
Select change in the menu and confirm
with OK.
Select signalling in the CHANGE menu
and confirm with OK.
Select remote in the SIGNALING menu
and confirm with OK.
Select fault relay in the SIGNALING menu
and confirm with OK.
Including additional faults
Included faults which cannot be altered are shown without brackets. Options
are in brackets and selections are shown with an asterisk *.
Turn to OK again to cancel selection.
Alarms
power off
fuse
thermal overload
lost phase
motor blocked
(jammed valve)
selector on local
selector on off
(emergency command)
(command override)
(overtravel)
(lost signal)
(p.t. fault)
English
loss of power on control circuit
blown fuse
thermal relay tripped
phase missing on 3-phase supply
motor immobilized
movement cannot be completed due to excessive
torque
local / remote selector on local
local / remote selector on off
actuator has received an emergency
command actuator has received command override
position overshoot >5% after motor cut off.
4-20 mA signal lost (if positioner option active)
A partial stroke operating error has occurred following
start of partial travel test, or it has not been possible
to perform test as the valve was not in the expected
position.
44
DEFAULT RELAY
return
power off
fuse
termal overload
...
Details