10 LOCAL CONTROL USING BUTTONS AND
DISPLAY
The local control facility provides a means
of operating the actuator electrically
without using an external control circuit.
There is a red knob for selecting remote
control, local control or disabled (off).
This knob can be locked in the 3 positions
using a 6 mm padlock.
The local open/close blue knob is used to
operate the actuator in the direction
required. Movement can be halted
locally by turning the local/ remote
selector switch briefly to the STOP
position.
The display shows the position of the
valve as a percentage of opening when it
is partially open.
The display shows "Closed" when the valve is closed. The display shows
"Open" when the valve is open.
The display is factory set to show the instantaneous torque as a percentage
of the maximum actuator torque value
< 10% indicates the minimum torque value.
Symbols that may appear on the display:
A remote command inhibits the local controls (see §14.2)
The actuator receives an emergency shutdown command (see
ESD
§14.2)
An infrared link is detected (see §15.1)
A bluetooth link is detected (Option: alternative solution to
infrared link : see §15.2)
indicates the presence of an alarm. (see §20.2 for the types of
alarm
With the battery option, the icon blinks if the battery voltage is
low.
English
Torque 60%
15
20% Open
Closed
Open