12.2 Automatic set-up
During automatic setting, the actuator halts on mechanical stops
so take care according the type of valves you are commissioning
Select SET UP in the MENU and validate with OK.
In the SET UP menu, select closing mode in the SET UP menu and
validate with OK.
Select if the valve is required to close on torque or on position and
confirm with OK.
In the SET UP menu, select close direction and validate with OK.
Select close direction (usually clockwise) and confirm with OK.
In the SET UP menu, select position setting and validate with OK.
Select automatic and confirm with OK.
The automatic setting cycle begins.
The cycle can be halted immediately during automatic set
up. Use the local stop command to return to the menu.
This action cancels the set-up procedure.
The actuator detects the end positions by means of the torque
limiter and then positions itself at mid-stroke to test its inertia in
both directions of travel.
INTELLI+ determines stop positions at 0 and 100% based on the
closing mode setting and the actuator inertia.
The display shows the stroke travel distance at the end of the
setup process.
Confirm with OK and get back to control mode.
English