25 USING FIELDBUS CONTROL (DEPENDING ON
MODEL)
The fieldbus interface is used for sending commands and data over a single
line. Specific documentation details methods for addressing individual
actuator and provides a list of addresses for accessing all commands or data
sources. The type of interface is shown in the menu.
Lost communication can be used to configure the fail-safe position. This
function is active in the standard configuration, and the actuator remains in
position if communication is lost.
The user can also choose open or close.
Select change in the menu and turn to OK
to confirm
Select bus in the CHANGE menu and turn
to OK to confirm
Select lost communic in the BUS menu
and turn to OK to confirm.
Select the action required and turn to OK
to confirm.
•
Bus control: Bus control is normally selected. For equipment which
also uses a standard hardwired system, this configuration allows the
user to choose the command mode: either via bus or hard-wired
(see §6.1 and §6.2)
•
Slave no. Actuator address: All actuators must have different
addresses. The default address is 2.
Refer to specific documentation for further details on fieldbus interfaces
commissioning.
English
PROFIBUS
return
lost communication
running time
cmd by fieldbus
slave number
return
LOST COMMUNIC
(closing)
(stayput)
(opening)
54