Performance Approvals
18.4 FM performance approval for
DrägerSensor H
The DrägerSensor H
S and H
2
diffusion sensors measuring hydrogen sulfide (H
ambient air.
DrägerSensor H
S (6810435)
2
Examination Type P8100
1)
Interface
Environmental parameters
Humidity
Temperature
Storage temperature
2)
Enclosure protection
Range
Accuracy (whichever is
greater)
Accessory
Dust filter
Adapter kit
Standard
1) HART communication must not be used for safety-relevant communi-
cation.
2) After submersion and jet water the sensor must be replaced.
DrägerSensor H
S LC (6809610)
2
Examination Type P8100
1)
Interface
Environmental parameters
Humidity
Temperature
Storage temperature
2)
Enclosure protection
Range
Accuracy (whichever is
greater)
Accessory
Dust filter
Adapter kit
Standard
1) HART communication must not be used for safety-relevant communi-
cation.
2) After submersion and jet water the sensor must be replaced.
50
S and H
S LC
2
2
S LC are electrochemical
2
S) in
2
ETR 0400, 0401, 0500, 0501
4-20mA, relay
5 to 95%RH, non-condensing
-40/+65 °C (-40/149 °F)
0/+40°C (32/104°F)
IP 65/66/67
0-100 ppm
measurement uncertainly (of
meas. value) ≤ ±3 % or mini-
mum ≤ ±0.5 ppm
6809595
6810536
ANSI/ISA-92.00.01FM6340
ETR 0400, 0401, 0500, 0501
4-20mA, relay
5 to 95%RH, non-condensing
-20/+65 °C (-4/149 °F)
0/+40°C (32/104°F)
IP 65/66/67
0-100 ppm
measurement uncertainly (of
meas.value) ≤ ±3 % or mini-
mum ≤ ±0.5 ppm in the range
>50 ppm, ±10 % or ±3 ppm
6809595
6810536
ANSI/ISA-92.00.01FM6340
Instructions for use
®
|
8000 Series SW version ≥ 4.0.x
Dräger Polytron