Télécharger Imprimer la page

Dräger Polytron 8000 Serie Notice D'utilisation page 45

Masquer les pouces Voir aussi pour Polytron 8000 Serie:

Publicité

Les langues disponibles

Les langues disponibles

Operating current
®
Polytron
87x0 IR
without relay, non-
remote sensor
with relay, remote
sensor
16.5 General specifications
Polytron 8xx0 enclosure
Enclosure material
Enclosure guard
Display
1) Polytron 8100 EC NEMA 4X enclosure guard pending.
2) The IP degrees of protection do not cover the detection of a gas,
during or after exposure of the equipment to these conditions. In the
event of dust deposits and contact with water through immersion or a
jet of water, check the adjustment and functional integrity of the instru-
ment.
16.6 Environmental parameters
Further sensor specifications and influences can be found in
the instructions for use provided for the respective sensor.
The values for accessories and spare parts may deviate from
the values given here. Exact values can be found in the
corresponding manual. 800 -1200 P8200 CAT LC
Polytron 8xx0
Values in accordance with explosion protection testing
During operation:
Pressure
Humidity
Temperatures
Polytron 8100 EC
Polytron 8200 CAT
Polytron 8310 IR
Polytron 87x0 IR
Values according to performance approval
During operation:
Pressure
Humidity
Instructions for use
|
Dräger Polytron
330 mA
350 mA
Copper-free aluminum
1)
NEMA 4X
2)
IP 65/66/67
Resolution 128 x 64 pixels,
backlit
23.6 to 32.5 in. Hg (800 to
1100 hPa)
0 to 100 % RH, non-condensing
-40 to +70 °C (-40 to +158 °F)
-40 to +80 °C (-40 to +176 °F)
-40 to +65 °C (-40 to +149 °F)
-40 to +80 °C (-40 to +176 °F)
20.7 to 38.4 in. Hg (700 to
1)
1300 hPa)
0 to 95 % RH, non-condensing
®
8000 Series SW version ≥ 4.0.x
Polytron 8xx0
Temperatures
2)
Polytron 8100 EC
Polytron 8200 CAT
Polytron 8310 IR
Polytron 87x0 IR
During storage:
Pressure
Humidity
Temperature
Recommended storage
period
Values for relay option and installations with UL
approval
During operation:
Temperatures
Polytron 8200 CAT
Polytron 87x0 IR
1) Polytron 8200 CAT: 23.6 to 35.44 in. Hg (800 to 1200 hPa)
2) See 18.3, 18.3.2 and the instructions for use provided for the EC sen-
sor for the constraints of the maximum specification.
16.7 Tightening torques
Instrument threads
Enclosure cover
Sensor
Blind plugs
Ports (for conduits or
cable glands)
Docking Station blind
plugs
Docking Station
cable glands
Remote EC sensing
head
Field wiring terminals
Power supply, sig-
nals and relays
Grounding screw
Technical data
-40 to +65 °C (-40 to +149 °F)
-40 to +80 °C (-40 to +176 °F)
-40 to +65 °C (-40 to +149 °F)
-40 to +77 °C (-40 to +170 °F)
26.5 to 32.4 in. Hg (900 to
1100 hPa)
0 to 100 % RH, non-condensing
-20 to +65 °C (-4 to +149 °F)
5 years
-40 to +70 °C (-40 to +158 °F)
-40 to +70 °C (-40 to +158 °F)
≥44 in-lbs / ≥5 Nm
min. 266 in-lbs / min. 30 Nm
min. 266 in-lbs / min. 30 Nm
min. 443 in-lbs / min. 50 Nm
62 in-lbs / 7 Nm
70 in-lbs / 8 Nm
177 in-lbs ±9 in-lbs / 20 Nm
±1 Nm
4.4 - 7.0 in-lbs / 0.5 - 0.8 Nm
10.6 in-lbs / 1.2 Nm
|