Configuring the Output Turn-On/Turn-Off Sequence
Turn-on and turn-off delays control the turn-on and turn-off timing of the outputs in relation to each other.
Step 1 – Set the outputs:
Refer to steps 1 and 2 under
Step 2 – Configure the turn-on turn-off delays:
In power supply mode, press Output Settings to access the Output Settings – On/Off Delays. Enter the On Delays
and Off Delays for all outputs that will participate in the output on/off delay sequence. Values can range from 0 to
3600 seconds.
In Load mode, press Input Settings to access the Input Settings – On/Off Delays. Enter the On Delays and Off Delays
for all outputs that will participate in the output on/off delay sequence. Values can range from 0 to 1023 seconds.
Power Supply mode
Step 3 – Coupling selected outputs:
This step is only required if you will be including some outputs to participate in an output on/off delay
sequence or if you are coupling multiple instruments. If only a single output is to be used in the sequence, you
can skip this step.
From the menu, press On/Off Coupling to access the On/Off Coupling mode settings.
– Press Coup CH 1 to toggle between Off and On in order to turn off or on the coupling for Output 1.
82
Controlling the Outputs
and set the output values of all outputs that will be sequenced.