Télécharger Imprimer la page

Burkert 8136 Mode D'emploi page 60

Publicité

Les langues disponibles

Les langues disponibles

Range of the output signal
Signal resolution
Resolution, digital
Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
Max. output current
Starting current
Load
Damping (63 % of the input variable),
adjustable
HART output values according to HART 7.0
Ʋ PV (Primary Value)
Ʋ SV (Secondary Value)
Ʋ TV (Third Value)
Ʋ QV (Fourth Value)
Fulfilled HART specification
Further information on Manufacturer ID,
Device ID, Device Revision
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
Ʋ Temperature
Ʋ Relative humidity
Ʋ Air pressure
Installation reference conditions
Ʋ Min. distance to internal installations
Ʋ Reflector
Ʋ False reflections
Deviation with liquids
Default values, can be assigned individually
1)
LEVEL TRANSMITTER 8136 • 4 ... 20 mA/HART - two-wire
3.8 ... 20.5 mA/HART (default setting)
0.3 µA
< 1 mm (0.039 in)
22 mA
≤ 3.6 mA; ≤ 10 mA for 5 ms after switching on
see load diagram under Power supply
0 ... 999 s
1)
Lin. percent
Distance
Meas. reliability
Electronics temperature
7.0
See website of HART Communication Foundation
+18 ... +30 °C (+64 ... +86 °F)
45 ... 75 %
860 ... 1060 mbar/86 ... 106 kPa (12.5 ... 15.4 psig)
> 200 mm (7.874 in)
Flat plate reflector
Biggest false signal, 20 dB smaller than the useful signal
See following diagrams
11 Supplement
59