6 Set up with the display and adjustment module
Setup - Adjustment
Setup - Min. adjustment
38
ment conditions, this menu item offers you different options for vessel
bottom and ceiling in case of certain applications.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Since the radar sensor is a distance measuring instrument, the
distance from the sensor to the product surface is measured. For
indication of the real level, an allocation of the measured distance to
the percentage height must be carried out.
To perform the adjustment, enter the distance with full and empty ves-
sel, see the following example:
Fig. 25: Parameter adjustment example min./max. adjustment
1
Min. level = max. meas. distance
2
Max. level = min. meas. distance
3
Reference plane
If these values are not known, an adjustment with the distances of for
example 10 % and 90 % is possible. Starting point for these distance
specifications is always the seal surface of the thread or flange. You
can find specifications of the reference plane in chapter "Technical
data". By means of these settings, the real level will be calculated.
The real product level during this adjustment is not important, be-
cause the min./max. adjustment is always carried out without chang-
ing the product level. These settings can be made ahead of time
without the instrument having to be installed.
Proceed as follows:
LEVEL TRANSMITTER 8136 • 4 ... 20 mA/HART - two-wire
3
2
100%
1
0%

Publicité