Télécharger Imprimer la page

Burkert 8136 Mode D'emploi page 46

Publicité

Les langues disponibles

Les langues disponibles

Via the interface adapter
and HART
Prerequisites
LEVEL TRANSMITTER 8136 • 4 ... 20 mA/HART - two-wire
7
Setup with PACTware
7.1
Connect the PC
1
5
Fig. 26: Connecting the PC via HART to the signal cable
1
Sensor
2 HART resistance 250 Ω (optional depending on processing)
3 Connection cable with 2 mm pins and terminals
4 Processing system/PLC/Voltage supply
7.2
Parameter adjustment with PACTware
For parameter adjustment of the sensor via a Windows PC, the con-
figuration software PACTware and a suitable instrument driver (DTM)
according to FDT standard are required. The up-to-date PACTware
version as well as all available DTMs are compiled in a DTM Collec-
tion. The DTMs can also be integrated into other frame applications
according to FDT standard.
Note:
To ensure that all instrument functions are supported, you should
always use the latest DTM Collection. Furthermore, not all described
functions are included in older firmware versions. You can download
the latest instrument software from our homepage. A description of
the update procedure is also available in the Internet.
7.3
Saving the parameter adjustment data
We recommend documenting or saving the parameter adjustment
data via PACTware. That way the data are available for multiple use or
service purposes.
7 Setup with PACTware
4
2
3
45

Publicité

loading