Sensor orientation
Vessel installations
Agitators
LEVEL TRANSMITTER 8136 • 4 ... 20 mA/HART - two-wire
Socket diameter d
100 mm
150 mm
Socket diameter d
3"
4"
6"
In liquids, direct the sensor as perpendicular as possible to the prod-
uct surface to achieve optimum measurement results.
Fig. 13: Alignment in liquids
The mounting location of the radar sensor should be a place where no
other equipment or fixtures cross the path of the radar signals.
Vessel installations, such as e.g. ladders, limit switches, heating spi-
rals, struts, etc., can cause false echoes and impair the useful echo.
Make sure when planning your measuring point that the radar sensor
has a "clear view" to the measured product.
In case of existing vessel installations, a false echo storage should be
carried out during setup.
If large vessel installations such as struts or supports cause false
echoes, these can be attenuated through supplementary measures.
Small, inclined sheet metal baffles above the installations scatter the
radar signals and prevent direct interfering reflections.
Fig. 14: Cover flat, large-area profiles with deflectors
If there are agitators in the vessel, a false signal storage should be
carried out with the agitators in motion. This ensures that the interfer-
ing reflections from the agitators are saved with the blades in different
positions.
Socket length h
≤ 400 mm
≤ 500 mm
Socket length h
≤ 11.8 in
≤ 15.8 in
≤ 19.7 in
4 Mounting