Additional adjustments -
False signal suppression
LEVEL TRANSMITTER 8136 • 4 ... 20 mA/HART - two-wire
changes over the operating time. In addition, the echo curve of the
setup can be also displayed in the echo curve window and compared
with the actual echo curve.
The following circumstances cause interfering reflections and can
influence the measurement:
•
High sockets
•
Vessel installations such as struts
•
Agitators
•
Buildup or welded joints on vessel walls
Note:
A false signal suppression detects, marks and saves these false
signals so that they are no longer taken into account in the level
measurement.
This should be done with a low level so that all potential interfering
reflections can be detected.
Proceed as follows:
1. Select with [->] the menu item "False signal suppression" and
confirm with [OK].
2. Confirm again with [OK].
3. Confirm again with [OK].
4. Confirm again with [OK] and enter the actual distance from the
sensor to the product surface.
5. All interfering signals in this section are detected by the sensor
and stored after confirming with [OK].
6 Set up with the display and adjustment module
41