9 Diagnosis, asset management and service
Function check
Out of specification
Maintenance
50
Code
Cause
Text mes-
sage
F261
– Error during setup
– False signal suppression
Error in the
faulty
instrument
settings
– Error when carrying out a
reset
F264
– Adjustment not within the
vessel height/measuring
Installation/
range
Setup error
– Max. measuring range of
the instrument not sufficient
F265
– Sensor no longer carries
out a measurement
Measurement
– Operating voltage too low
function dis-
turbed
The following table shows the error codes and text messages in the
status message "Function check" and provides information on causes
as well as corrective measures.
Code
Cause
Text mes-
sage
C700
– A simulation is active
Simulation ac-
tive
The following table shows the error codes and text messages in the
status message "Out of specification" and provides information on
causes as well as corrective measures.
Code
Cause
Text mes-
sage
S600
– Temperature of the elec-
tronics in the non-specified
Impermissi-
range
ble electronics
temperature
S601
– Danger of vessel overfilling
Overfilling
S603
– Operating voltage below
specified range
Impermissi-
ble operating
voltage
The following table shows the error codes and text messages in the
status message "Maintenance" and provides information on causes
as well as corrective measures.
LEVEL TRANSMITTER 8136 • 4 ... 20 mA/HART - two-wire
Rectification
– Repeat setup
– Carry out a reset
– Check or correct installation
and/or parameter adjust-
ment
– Use an instrument with big-
ger measuring range
– Check operating voltage
– Carry out a reset
– Disconnect operating volt-
age briefly
Rectification
– Finish simulation
– Wait for the automatic end
after 60 mins.
Rectification
– Check ambient temperature
– Isolate electronics
– Use instrument with higher
temperature range
– Make sure that there is no
further filling
– Check level in the vessel
– Check electrical connection
– if necessary, increase
operating voltage