4 Mounting
Surge pipe extension
Instructions and require-
ments, surge pipe
20
1
Fig. 17: Welding connection with surge pipe extension for different example
diameters
1
Position of the welded joint with longitudinally welded pipes
Instructions of orientation of the polarisation:
Note marking of the polarisation on the sensor
With threaded versions, the marking is on the hexagon, with flange
versions between two flange holes
The marking must be in one plane with the holes in the surge pipe
Instructions for the measurement:
The 100 % point must be below the upper vent hole and the
antenna edge
The 0 % point is the end of the surge pipe
During parameter adjustment, select "Application standpipe" and
enter the tube diameter to compensate for errors due to running
time shift
A false signal suppression with the installed sensor is recom-
mended but not mandatory
The measurement through a ball valve with unrestricted channel
is possible
LEVEL TRANSMITTER 8136 • 4 ... 20 mA/HART - two-wire
ø 88,9 mm
(3.5")
26 mm
(1.02")
2 mm
(0.08")
5 mm
(0.20")