Flow measurement with
rectangular flume
LEVEL TRANSMITTER 8136 • 4 ... 20 mA/HART - two-wire
Constructional requirements on the bypass pipe:
Material metal, smooth inner surface
In case of an extremely rough tube inner surface, use an inserted
tube (tube in tube) or a radar sensor with tube antenna
Flanges are welded to the tube according to the orientation of the
polarisation
Gap size with junctions ≤ 0.1 mm, for example, when using a ball
valve or intermediate flanges with single pipe sections
The antenna diameter of the sensor should correspond to the
inner diameter of the tube
Diameter should be constant over the complete length
4.6
Measurement setup - Flow
The short examples give you introductory information on the flow
measurement. Detailed planning information is available from flume
manufacturers and in special literature.
3 ... 4 h
max
90°
2
2
Fig. 19: Flow measurement with rectangular flume: d
sensor (see chapter "Technical data"); h
flume
1 Overflow orifice (side view)
2
Headwater
3
Tail water
4 Overfall orifice (view from bottom water)
In general, the following points must be observed:
Install the sensor on the headwater side
Installation in the centre of the flume and vertical to the liquid
surface
Distance to the overfall orifice
Distance of orifice opening above ground
Min. distance of the orifice opening to bottom water
Min. distance of the sensor to max. storage level
1
≥ 50 mm
3
3
= max. filling of the rectangular
max.
4 Mounting
90°
4
= min. distance of the
min.
23