LEVEL TRANSMITTER 8136 • 4 ... 20 mA/HART - two-wire
The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-
ment from the factory incl. the order-specific settings. A created false
signal suppression, user-programmable linearization curve as well as
the measured value memory will be deleted.
Basic settings: Resetting of the parameter settings, incl. special
parameters, to the default values of the respective instrument. Any
stored false signal suppression or user programmable linearisation
curve, as well as the measured value memory, is deleted.
Setup: Resetting of the parameter settings to the default values of the
respective instrument in the menu item Setup. User-generated false
signal suppression, user-programmed linearisation curve, measured
value memory as well as event memory remain untouched. The
linearisation is set to linear.
False signal suppression: Deleting a previously created false signal
suppression. The false signal suppression created in the factory
remains active.
Peak values, measured value: Resetting of the measured min. and
max. distances to the actual measured value.
The following table shows the default values of the instrument. De-
pending on the instrument version, not all menu items are available or
some may be differently assigned:
Menu
Menu item
Setup
Measurement
loop name
Medium
Application
Vessel form
Vessel height/
Measuring range
Min. adjustment
Max. adjustment
Damping
Current output
mode
Current output
Min./Max.
Lock adjustment
6 Set up with the display and adjustment module
Default value
Sensor
Liquid/Water
Bulk solids/Crushed stones, gravel
Storage tank
Silo
Vessel bottom, dished boiler end
Vessel top, dished boiler end
Recommended measuring range, see
"Technical data" in the supplement
Recommended measuring range, see
"Technical data" in the supplement
0,000 m(d)
0.0 s
4 ... 20 mA, < 3.6 mA
Min. current 3.8 mA, max. current
20.5 mA
Released