4 Mounting
Configuration bypass
Instructions and require-
ments, bypass
22
4
100 %
5
0 %
Fig. 18: Configuration bypass
1
Radar sensor
2 Polarisation marking
3 Instrument flange
4
Distance sensor reference plane to upper tube connection
5
Distance of the tube connections
6
Ball valve with complete opening
Instructions of orientation of the polarisation:
•
Note marking of the polarisation on the sensor
•
With threaded versions, the marking is on the hexagon, with flange
versions between two flange holes
•
The marking must be in one plane with the tube connections to the
vessel
Instructions for the measurement:
•
The 100 % point may not be above the upper tube connection to
the vessel
•
The 0 % point may not be below the lower tube connection to the
vessel
•
Min. distance, sensor reference plane to upper edge of upper tube
connection > 300 mm
•
During parameter adjustment, select "Application standpipe" and
enter the tube diameter to compensate for errors due to running
time shift
•
A false signal suppression with the installed sensor is recom-
mended but not mandatory
•
The measurement through a ball valve with unrestricted channel
is possible
LEVEL TRANSMITTER 8136 • 4 ... 20 mA/HART - two-wire
1
2
3
6