Télécharger Imprimer la page

Burkert 8136 Mode D'emploi page 34

Publicité

Les langues disponibles

Les langues disponibles

LEVEL TRANSMITTER 8136 • 4 ... 20 mA/HART - two-wire
– Slight sensitivity against sporadic false echoes
– Stable and reliable measured values through averaging
– High accuracy because not adjusted for max. speed
– False signal suppression recommended
Storage tank on ships (Cargo Tank):
Product speed: slow filling and emptying
Vessel:
– Installations in the bottom section (bracers, heating spirals)
– High sockets 200 ... 500 mm, also with large diameters
Process/measurement conditions:
– Condensation, buildup by movement
– Max. requirement on measurement accuracy from 95 %
Properties, sensor:
– Slight sensitivity against sporadic false echoes
– Stable and reliable measured values through averaging
– High accuracy
– False signal suppression required
Stirrer vessel (reactor):
Setup: all vessel sizes possible
Product speed:
– Fast to slow filling possible
– Vessel is very often filled and emptied
Vessel:
– Socket available
– Large agitator blades of metal
– Vortex breakers, heating spirals
Process/measurement conditions:
– Condensation, buildup by movement
– Strong spout generation
– Very agitated surface, foam generation
Properties, sensor:
– Higher measurement speed through lower averaging
– Sporadic false echoes are suppressed
Dosing vessel:
Setup: all vessel sizes possible
Product speed:
– Fast filling and emptying
– Vessel is very often filled and emptied
Vessel: narrow installation situation
Process/measurement conditions:
– Condensation, buildup on the antenna
– Foam generation
Properties, sensor:
– Measurement speed optimized by virtually no averaging
– Sporadic false echoes are suppressed
– False signal suppression recommended
Standpipe:
Product speed: very fast filling and emptying
Vessel:
6 Set up with the display and adjustment module
33

Publicité

loading