9 Diagnosis, asset management and service
Treatment of measure-
ment errors with liquids
52
Error
Cause
4 ... 20 mA signal
– Fluctuations of
not stable
the measured
variable
4 ... 20 mA signal
– Electrical con-
missing
nection faulty
– Voltage supply
missing
– Operating volt-
age too low or
load resistance
too high
Current sig-
– Electronics
nal greater than
module in the
22 mA or less
sensor defec-
than 3.6 mA
tive
The below tables show typical examples of application-related meas-
urement errors with liquids. The measurement errors are differentiated
according to the following:
Constant level
Filling
Emptying
The images in column "Error pattern" show the real level with a bro-
ken line and the level displayed by the sensor as a continuous line.
1
Real level
2
Level displayed by the sensor
Notes:
Wherever the sensor displays a constant value, the reason could
also be the fault setting of the current output to "Hold value"
If the level indication is too low, the reason could be a line resist-
ance that is too high
LEVEL TRANSMITTER 8136 • 4 ... 20 mA/HART - two-wire
Rectification
– Set damping according to the
instrument via the display and
adjustment module or PACTware/
DTM
– Check connection according to
chapter "Connection steps" and
if necessary, correct according to
chapter "Wiring plan"
– Check cables for breaks; repair if
necessary
– Check, adapt if necessary
– Exchange the instrument or send it
in for repair