12. Parameter configuration
12.1. Available parameters
Various operating parameters can be freely changed in the control system.
Parameter
Parameter function
no.
Heating zone 1 output:
Display of the kiln output to
14
determine the energy
consumption in kWh
Heating zone 2 output:
Display of the kiln output to
24
determine the energy
consumption in kWh
Heating zone 3 output:
Display of the kiln output to
34
determine the energy
consumption in kWh
Additional switch output 1
45
230 V
(ST 632 only)
Additional switch output 2
49
230 V
(ST 632 only)
Logging interval data on
50
USB in s
Temperature display in °C
60
or °F
Notes:
*1: For kilns with 1 heating zone, only parameter no. 14 can be changed instead of nos. 24 and 34 as well.
*2: For kilns with 3 heating zones, the power specified on the kiln nameplate is evenly distributed across the 3 heating
zones (e.g. in a kiln with 3 zones and 30 kW, each heating zone has 10 kW).
Min.
Max.
Default
value
value
setting
0
9999
0
0
9999
0
0
9999
0
0
1
1
0
1
1
5
300
60
0
1
0
86 / 317 - EN -
Description of the value
1 unit = 0.1 kW
E.g.:
⇒ For a kiln with 1 heating zone and a
total output of 10 kW (see kiln
nameplate), enter the value "100"
here.
⇒ For a kiln with 3 heating zones and
a total output of 30 kW (see kiln
nameplate), each individual heating
zone usually has 10 kW and
therefore enter the value "100"
here.
1 unit = 0.1 kW
E.g.:
⇒ For a kiln with 3 heating zones and
a total output of 30 kW (see kiln
nameplate), each individual heating
zone usually has 10 kW and
therefore enter the value "100"
here.
1 unit = 0.1 kW
E.g.:
For a kiln with 3 heating zones and a
total output of 30 kW (see kiln
nameplate), each individual heating
zone usually has 10 kW and therefore
enter the value "100" here.
0 = disabled
1 = event
2/3 = ATTENTION: Parameter 2 or 3
must not be used if it is available!!!
0 = disabled
1 = event
2 = ATTENTION: Parameter 2 must
not be used if it is available!!!
1 unit = 1 s (second)
0 =°C
1 = °F